BS 5950 earilier code

We have the requirement of adequacy check of existing piperack built in 1991. Could you pls add the code BS 5950 1990 so that we can present to client that we complied the requirement of checking the existing structure with existing codal requirement.

  • Admin
    Carlos Aguera
    Aug 7, 2026

    Thank you for posting this idea. As you know, although the design code BS 5950 has been withdrawn. we do still include it as a legacy code from the 2000 edition. Providing implementation for older versions of the code is not viable. If the structure fails to the 2000 version of the code, I would suggest that is worth a longer conversation with the client than validating that it complies with the 1991 edition.